4 Technical Data
130
6MD665 Manual
C53000-G1876-C103-3
Output relays
1)
depends on order variant
4.1.4
Communication interfaces
Operator Interface
Service / Modem
Interface
for rated voltages
220 to 250 V DC
Upu
≥
176 V DC
Udo
≤
132 V DC
Maximum permissible voltage
300 V DC
Impulse filter on input
220 nF at 220 V with recovery time > 60 ms
Flag/command relay
Number
7 to 12 (allocatable)
1)
Contacts per relay
1 NO contact
Switching capability ON
1000 W/VA
1
)
Switching capability OFF
30 VA
40 W resistive
25 W/VA at L/R
≤
50ms
Switching voltage
250 V
Permissible current per contact / inrush
peak
5 A continuous
30 A
≤
0.5 s
Permissible current per contact
On common path
5 A continuous 30 A for 0.5 s
Life contact
1 with 1 NO contact or 1 NC contact (switchable)
Switching capability ON
30 W/VA
Switching capability OFF
20 VA
30 W resistive
25 W at L/R
≤
50 ms
Switching voltage
250 V
Permissible current
1 A continuous
Connection
front side, non-isolated, RS 232, 9 pin DSUB port for
connecting a personal computer
Operation
with DIGSI
®
Transmission Speed
min. 4 800 Baud; max. 115 200 Baud; factory setting:
38 400 Baud; Parity: 8E1
Maximum Distance of Transmission
49 feet (15 m)
General
Connection
isolated interface for data transfer
Operation
with DIGSI
®
Содержание SIPROTEC 6MD665
Страница 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Страница 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Страница 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Страница 201: ...A 9 Group Alarms 187 6MD665 Manual C53000 G1876 C103 3 A 9 Group Alarms No Description No Description ...
Страница 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Страница 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...