3.1 Installation and Connections
101
6MD665 Manual
C53000-G1876-C103-3
3.1.2.3
Switching elements on the PCBs
I/O-1 module
Check the set rated voltage of the integrated power supply, the quiescent state of the life con-
tact, the selected control voltages of binary inputs BI1 to BI8 using the layout of the PCB of the
input/output module I/O-1 and the tables below.
Figure 3-3
I/O-1 input/output module with representation of the jumpers required for checking the settings
Table 3-1
Jumper setting of the rated voltage of the integrated power supply on the input/
output module I/O-1
Jumper
Rated voltage
24 to 48 V DC
60 V DC
110 V DC
220 to 250 V DC
X51
Not used
1–2
1–2
2–3
X52
Not used
1–2 and 3–4
1–2 and 3–4
2–3
X53
Not used
1–2
1–2
2–3