Figure 2-9
Power measurement at generator
If you have the choice to assign a side or a measuring location to the main protected object as shown in
(S1 is identical to M1), such assignment of the side is preferable, because the power can be set
later directly in the (mostly known) reference values. As the nominal data of the main protected object are
known to the device, no conversion of reference values to secondary values will be required.
The under- and overvoltage protection and the frequency protection also use the voltages connected to the
device. Select the side or measuring location here, which is electrically connected to the voltage transformer
set.
Should the voltages not be required for the protection functions, select the voltages that must be indicated or
transferred as operational measured values during operation, or on the basis of which you wish to calculate
the power.
For the 1-phase voltage measurement input U4, likewise a side or measuring location can be selected at
address 262
VT U4
- irrespective of the assignment of the 3-phase voltage inputs. This measuring input is
frequently used for the displacement voltage, measured at the e-n windings of the voltage transformer set,
but you can also use it for detection of any other measured voltage. In this case set
VT U4
=
conn/not
assig.
(connected, but not assigned). If no voltage is needed at the 1-phase voltage input, set
Not
connected
(not connected).
As different connections are possible, you must now specify in the device how the connected 1-phase voltage
should be interpreted. This is done at address 263
VT U4 TYPE
. Set
Udelta transf.
if the voltage
assigned acc. to address 262 is a displacement voltage. It can also be any phase-to-earth voltage (e.g.
UL1E
transform.
), or a phase-to-phase voltage (e.g.
UL12 transform.
). If U4 is connected to a voltage which
is assigned to no side or measuring location, set
Ux transformer
.
General Power System Data
General
The device requires some plant and power system data in order to be able to adapt its functions accordingly,
dependent on the actual application. The data required include for instance rated data of the substation and
the measuring transformers, polarity and connection of the measured quantities, if necessary features of the
circuit breakers, and others. There are also certain parameters common to all functions, i.e. not associated
with a specific protection, control or monitoring function. These data can only be changed from a PC running
DIGSI and are discussed in this section.
Rated Frequency
The rated frequency of the power system is set under address 270
Rated Frequency
. The available rated
frequencies are
50 Hz
,
60 Hz
and
16,7 Hz
(7UT613/63x).
Phase Sequence
Under address 271
PHASE SEQ.
the presetting for clockwise rotation
L1 L2 L3
can be changed if a power
plant has an anticlockwise rotation
L1 L3 L2
. The phase sequence has no influence on the vector group
conversion of the differential protection as long as the identical phase rotation is present on all sides of the
protected object. This setting is irrelevant for single-phase application and is not accessible.
2.1.4.2
Functions
2.1 General
SIPROTEC 4, 7UT6x, Manual
55
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...