Average Values, Minimum and Maximum Values
Average, minimum and maximum values, minimum and maximum values of average values, long-term
average values, are calculated by the 7UT6x and can be read out with the time reference (date and time of the
last update).
The defined values of the average values and minimum and maximum values are to be defined and up to 20
calculation units can be created with the help of DIGSI under menu item “Extended Measuring Values 1-20” in
menu “Functional Scope”.
The parameter “Input Variable” determines the measured value for which the calculation unit calculates the
average values and the minimum/maximum values.
The following can be selected: phase currents of the measuring locations and sides, voltages, power values,
residual currents, frequency and differential protection values. Selection of the input value varies depending
on the protection device 7UT6x and the settings of the configuration parameters.
With the parameter “Scope of the Extended Measured Values”, it can be determined whether calculation units
are to calculate average values, minimum and maximum values or minimum and maximum values of long-
term average values, or a combination thereof.
Extent of the extended measured values
Min/Max
Min/Max/Average
Min/Max/A Min/Max of
Average
Average
A Min/Max of Average
[minwax-werte, 1, en_GB]
The calculated average values and minimum/maximum values appear in the device menu “Measured Values”
in the menus “MV Measured Values”, “Average, Min/Max” and “MV, Min/Max” and in DIGSI in the menus
“Minimum and Maximum Values”, “Average Values” and “Minimum and Maximum Values of the Average
Values” under menu “Min/Max and Average Values” in menu “Measured Values”.
The results of the calculation unit can be reset via the set message/binary input message in parameter “Reset-
ting of the ext. Measured Values” or via DIGSI, or the integrated control panel.
Demand Measurement Setup
Setting Notes
Mean Value Formation
The synchronisation instant within one hour, the time interval and the time interval for averaging can be set
via parameters.
The selection of the time period for measured value averaging is set with parameter 7611
DMD Interval
in
the corresponding setting group from A to D under MEASUREMENT. The first number specifies the averaging
time window in minutes while the second number gives the frequency of updates within the time window.
15
Min., 3 Subs
, for example, means: Time average is generated for all measured values with a window of 15
minutes. The output is updated every 15/3 = 5 minutes.
2.23
2.23.1
2.23.1.1
Functions
2.23 Average Values, Minimum and Maximum Values
SIPROTEC 4, 7UT6x, Manual
301
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...