Differential and Restraining Measured Values
Depending on its configuration, the device calculates the measured values that are specific to differential
protection.
Functional Description
The differential and restraining values of the differential protection and the restricted earth fault protection
are listed in table
. They always refer to the nominal current of the main protected object, which
results from the parameterised nominal data of the main protected object (Section
). For multi-winding transformers with different winding ratings, the most powerful winding is deci-
sive, for busbars and lines the nominal operation current as set for the protected object. In case of 1-phase
busbar protection, only the values of the connected and declared phase are displayed.
In case of restricted earth fault protection, the nominal phase currents provide the reference value.
Table 2-16
Measured values of differential protection
Measured Values
% referred to
Ι
DiffL1,
Ι
DiffL2,
Ι
DiffL3
Calculated differential currents of the three phases
Operational rated current of the
protected object
Ι
RestL1,
Ι
RestL2,
Ι
RestL3
Calculated restraining currents of the three phases
Operational rated current of the
protected object
Ι
DiffEDS
Calculated differential current of the restricted earth
fault protection
Rated operational current of the
side or 3-phase measuring loca-
tion
Ι
RestEDS
Calculated restraint current of the restricted earth
fault protection
Rated operational current of the
side or 3-phase measuring loca-
tion
Information List
No.
Information
Type of
Informa-
tion
Comments
199.2640 IdiffREF=
MV
Idiff REF (I/Inominal object [%])
199.2641 IrestREF=
MV
Irest REF (I/Inominal object [%])
205.2640 IdiffRE2=
MV
Idiff REF2 (I/Inominal object [%])
205.2641 IrestRE2=
MV
Irest REF2 (I/Inominal object [%])
7742
IDiffL1=
MV
IDiffL1(I/Inominal object [%])
7743
IDiffL2=
MV
IDiffL2(I/Inominal object [%])
7744
IDiffL3=
MV
IDiffL3(I/Inominal object [%])
7745
IRestL1=
MV
IRestL1(I/Inominal object [%])
7746
IRestL2=
MV
IRestL2(I/Inominal object [%])
7747
IRestL3=
MV
IRestL3(I/Inominal object [%])
2.22.4
2.22.4.1
2.22.4.2
Functions
2.22 Auxiliary Functions
SIPROTEC 4, 7UT6x, Manual
287
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...