Addr.
Parameter
C
Setting Options
Default Setting
Comments
2112
I>>
0.10 .. 35.00 I/InS; ∞
10.00 I/InS
I>> Pickup
2113
T I>>
0.00 .. 60.00 sec; ∞
0.10 sec
T I>> Time Delay
2114
I>
1A
0.10 .. 35.00 A; ∞
4.00 A
I> Pickup
5A
0.50 .. 175.00 A; ∞
20.00 A
2115
I>
0.10 .. 35.00 I/InS; ∞
4.00 I/InS
I> Pickup
2116
T I>
0.00 .. 60.00 sec; ∞
0.30 sec
T I> Time Delay
2121
Ip
1A
0.10 .. 4.00 A
4.00 A
Ip Pickup
5A
0.50 .. 20.00 A
20.00 A
2122
Ip
0.10 .. 4.00 I/InS
4.00 I/InS
Ip Pickup
2123
T Ip
0.05 .. 3.20 sec; ∞
0.50 sec
T Ip Time Dial
2124
D Ip
0.50 .. 15.00 ; ∞
5.00
D Ip Time Dial
Information List
No.
Information
Type of
Informa-
tion
Comments
023.2404 >BLK Phase O/C
SP
>BLOCK Phase time overcurrent
023.2411 O/C Phase OFF
OUT
Time Overcurrent Phase is OFF
023.2412 O/C Phase BLK
OUT
Time Overcurrent Phase is BLOCKED
023.2413 O/C Phase ACT
OUT
Time Overcurrent Phase is ACTIVE
023.2422 O/C Ph L1 PU
OUT
Time Overcurrent Phase L1 picked up
023.2423 O/C Ph L2 PU
OUT
Time Overcurrent Phase L2 picked up
023.2424 O/C Ph L3 PU
OUT
Time Overcurrent Phase L3 picked up
023.2491 O/C Ph. Not av.
OUT
O/C Phase: Not available for this object
023.2501 >BLK Ph.O/C Inr
SP
>BLOCK time overcurrent Phase InRush
023.2502 >BLOCK I>>
SP
>BLOCK I>>
023.2503 >BLOCK I>
SP
>BLOCK I>
023.2504 >BLOCK Ip
SP
>BLOCK Ip
023.2514 I>> BLOCKED
OUT
I>> BLOCKED
023.2515 I> BLOCKED
OUT
I> BLOCKED
023.2516 Ip BLOCKED
OUT
Ip BLOCKED
023.2521 I>> picked up
OUT
I>> picked up
023.2522 I> picked up
OUT
I> picked up
023.2523 Ip picked up
OUT
Ip picked up
023.2524 I> InRush PU
OUT
I> InRush picked up
023.2525 Ip InRush PU
OUT
Ip InRush picked up
023.2526 L1 InRush PU
OUT
Phase L1 InRush picked up
023.2527 L2 InRush PU
OUT
Phase L2 InRush picked up
023.2528 L3 InRush PU
OUT
Phase L3 InRush picked up
023.2531 L1 InRush det.
OUT
Phase L1 InRush detected
023.2532 L2 InRush det.
OUT
Phase L2 InRush detected
023.2533 L3 InRush det.
OUT
Phase L3 InRush detected
023.2534 INRUSH X-BLK
OUT
Cross blk: PhX blocked PhY
023.2541 I>> Time Out
OUT
I>> Time Out
023.2542 I> Time Out
OUT
I> Time Out
023.2543 Ip Time Out
OUT
Ip Time Out
023.2551 I>> TRIP
OUT
I>> TRIP
2.4.2.3
Functions
2.4 Time Overcurrent Protection for Phase and Residual Currents
154
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Содержание SIPROTEC 4 7UT6 Series
Страница 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Страница 683: ...Z Zero sequence currents 109 Index SIPROTEC 4 7UT6x Manual 683 C53000 G1176 C230 5 Edition 09 2016 ...
Страница 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...