Flexible Protection Functions
The flexible protection function is applicable for a variety of protection principles. The user can create up to 20
flexible protection functions and configure them according to their function. Each function can be used either
as an autonomous protection function, as an additional protective element of an existing protection function
or as a universal logic, e.g. for monitoring tasks.
Functional Description
General
The function is a combination of a standard protection logic and a characteristic (measured quantity or derived
quantity) that is adjustable via parameters. The characteristics listed in
and the derived protection
functions are available.
Please note that no power values or frequency values are available if you are not using a voltage connection.
Table 2-6
Possible Protection Functions
Characteristic
Group
Characteristic / Measured Quantity
Protective Function
ANSI-No.
Mode of Operation
3-phase 1-phase
Current
Ι
RMS value of fundamental
component
Overcurrent protection
Undercurrent monitoring
50, 50G
37
X
X
Ι
rms
True RMS (r.m.s. value)
Overcurrent protection
Thermal overload protec-
tion
Undercurrent monitoring
50, 50G
37
X
X
3
Ι
0
Zero sequence system
Time overcurrent protec-
tion, ground
50N
X
Ι
1
Positive-sequence component
X
Ι
2
Negative-sequence component
Negative sequence protec-
tion
46
X
Ι
2/
Ι
1
Positive/negative sequence
component ratio
X
Frequency
f
Frequency
Frequency protection
81U/O
without phase
reference
df/dt
Frequency change
Frequency change protec-
tion
81R
Voltage
V
RMS value of fundamental
component
Voltage protection
Displacement voltage
27, 59,
59G
X
X
V
rms
True RMS (r.m.s. value)
Voltage protection
Displacement voltage
27, 59,
59G
X
X
3V
0
Zero sequence system
Displacement voltage
59N
X
V
1
Positive-sequence component
Voltage protection
27, 59
X
V
2
Negative-sequence component
Voltage asymmetry
47
X
dV/dt Voltage change
Voltage change protection 27R, 59R
X
Power
P
Real power
Reverse power protection
Power protection
32R, 32, 37
X
X
Q
Reactive power
Power protection
32
X
X
cos φ Power factor
Power factor
55
X
X
Binary input
–
Binary input
Direct coupling
without phase
reference
2.15
2.15.1
Functions
2.15 Flexible Protection Functions
SIPROTEC 4, 7SD80, Manual
167
E50417-G1100-C474-A2, Edition 02.2018
Содержание SIPROTEC 4 7SD80
Страница 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Страница 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...