Configuration
8.5 Configuration control (option handling)
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
123
8.5.3.5
Behavior during operation
Response when modules are missing
If modules are entered as not present in the control data record, the automation system
behaves as follows:
●
Modules designated as not present in the control data record do not supply diagnostics
and their status is always OK. The value status is OK.
●
Direct write access to the outputs that are not present or write access to the process
image of the outputs that are not present: Remains without effect; no access error is
signaled.
●
Direct read access to the inputs that are not present or read access to the process image
of the inputs that are not present: Value "0" is supplied; no access error is signaled.
Note
The configuration from the control data record DS196 must match the configuration of the
HCS that actually exists.
Otherwise no startup can take place.