SIPLUS CMS2000 shield support; for correct EMC connection of 
signal and encoder cables to the basic unit VIB.

Additional strain release of the cables is required.

 WARNING

These instructions as well as the operating instructions must be read and 

understood before installation, operation or maintenance of the SIPLUS 

CMS2000. 

The product/system belonging to this documentation may only be  

handled by personnel qualified for the respective task in hand, paying 

attention to the SIPLUS CMS2000 operating instructions  

(http://www.siemens.com/automation/service&support), in particular the 

safety and warning notes contained therein. 

Qualified personnel are those who, based on their training and experience, 

are capable of identifying risks and avoiding potential hazards  

when working with these products/systems.

Contents

• 5 clamp connections
• 2 shielding clips
• Compact Operating Instructions

Mounting the shield support

6WUDQGVPP

)XQFWLRQDOJURXQG

VWDUSRLQW

6KLHOGLQJEUDLG

6KLHOGVXSSRUW

7HUPLQDOFODPS

/$1(WKHUQHW

$QDORJLQSXWV

6HQVRUVLJQDOV

)XQFWLRQDOJURXQGLQJ

Note

Only connect functional ground using the designated  

connections.

Attaching the cable shield

The following SIPLUS CMS2000 signals must be connected via 
shielded  
cables with their shields attached to the CMS2000 
side:
• Sensor signals (VIB1 / VIB2)
• Analog inputs (AI1 / AI2)
• LAN (Ethernet)

The shields of the cables must be attached to the upper and/or lower 
shield support using the clamp connections. To do this, proceed as  
follows:

1. Strip the cable.

Sensor signals (VIB1 / VIB2), analog inputs (AI1 / AI2)

10 mm

 

150 mm

1)

20 mm

LAN (Ethernet)

 

150 mm

1)

20 mm

1)

 Length depends on distance between shield support and device.

2. Press the clamp connection onto the protective braided shield of the cable.

3. Slide the clamp connection onto the shield support.

4. You can see the result in diagram 1 under "Mounting the shield support".

Note

Attach the cable shield on the device side no further than 15 cm away from 

the input terminal.

Note

To ensure fault-free operation, particularly with long cables,  

it is recommended to make a large area contact to ground potential for the shield 

at the far end of the cable as well. Ensure adequate equipotential bonding.