Installation
9229 0025 176 0E
51
2021-11-15
Connecting the low voltage for the withdrawable part
Laying the cable harness
(see Fig. 73)
• Feed the cable harness of the withdrawable part with the plugs (-Q0) along the
side wall through the vacuum circuit-breaker.
• Fix the cable harness to the existing cable harness using cable straps and
ensure there is sufficient distance from the spring state indicator.
Laying the cable harness
(see Fig. 74)
• Feed the cable harness of the withdrawable part with the plugs (-Q0) through
the vacuum circuit-breaker.
• Fix the cable harness to the right side wall with cable straps.
Mounting the plug
• Insert the plug bottom (-Q0) into the frame as far as it will go and let it engage.
• Wire the plug (-Q1) and insert it (see “Wiring of connectors Q0-X1.1, Q0-X1.2,
Fig. 73
Laying the cable harness
Fig. 74
Laying the cable harness
Fig. 75
Mounting the plug for the withdrawable part
Fig. 76
Mounting the plug for the withdrawable part