6.2.2
Connecting the power supply
Cable specification
DANGER
Protective separation
The 24 V direct voltage must be configured as an extra-low-voltage with protective separation
- DVC A or PELV.
The required 24 VDC load power supply is wired to the screw-type terminal block (X1).
Use flexible cables with a cross-section of 0.25 to 2.5 mm
2
(or AWG 23 to AWG 13) for wiring
the power supply according to the maximum occurring current.
If you only use one wire per connection, a ferrule is not required. The following wire-end ferrules
are permissible: Without an insulating collar in accordance with DIN 46228, Form A, long
version
Table 6-4
Cable specification for X1
Features
Version
Connection option
Up to 2.5 mm
2
Current carrying capacity
max. 10 A
Max. cable length
10 m
6.3
Ethernet
X130, X127 pin assignment
Pin
Signal name
Signal type
Meaning
1
TX+
O
Transmit data +
2
TX-
O
Transmit data -
3
RX+
I
Receive data +
4
NC
-
5
NC
-
6
RX-
I
Receive data -
7
NC
-
8
NC
-
Interface description
6.3 Ethernet
PPU
Manual, 01/2014, 6FC5397-2DP40-3BA3
71