![Siemens Sinteso Cerberus PRO FDA221 Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/siemens/sinteso-cerberus-pro-fda221/sinteso-cerberus-pro-fda221_manual_383555007.webp)
7
Building Technologies
A6V10331032_j_en_--
Fire Safety
2019-01-24
Accessories
Communication interface FDCC221S
●
For connecting the aspirating smoke detector to FDnet/C-NET
●
Integrated 'line separator' function
●
Additional MC link interface (port for 3.5 mm jack)
●
Tool-free mounting on a designated PCB slot
●
Supplied with:
– 2x spacers with thread
– 4-pin plug-in terminal
– ID adhesive label
Power supply kit FP120-Z1
●
Standalone power supply (70 W)
●
Supply to external devices and components in accordance with EN 54-4 and
VdS
●
With operating and fault indicator, shown via a green and a yellow LED
●
With potential-free relay contacts for fault messages
●
Additional installation of an I/O module possible
●
Uninterruptible power supply with battery charging
●
Batteries: max. 17 Ah
●
Dimensions: (W x H x D) 430 x 399 x 124 mm
Battery FA2003-A1 (12 V, 7 Ah, VdS)
●
For supplying fire control panels and aspirating smoke detectors with power
●
Compatible with:
– Fire control panels for the 'Sinteso' and 'Cerberus PRO' product lines
– External power units for the aspirating smoke detectors FDA241 and
FDA221
Battery FA2004-A1 (12 V, 12 Ah, VdS)
●
For supplying fire control panels and aspirating smoke detectors with power
●
Compatible with:
– Fire control panels for the 'Sinteso' and 'Cerberus PRO' product lines
– External power units for the aspirating smoke detectors FDA241 and
FDA221