Siemens SINORIX CPY-35 Скачать руководство пользователя страница 1

 

 

Installation Instructions 

Document No. 129-097 

June 10, 2020 

 

SINORIX

™ Valve Reconditioning 

 

 

Item Number 129-097, Rev. BA

 

Page 1 of 6 

Product Description 

These instructions explain how to recondition and fill 
1-inch through 4-inch SINORIX valves.  

NOTE: 

Only for systems manufactured prior to 2014 
with integrated fixed valve releasing solenoid 
and local manual control (CPY-LMC). See 

Figure 3

 and 

Figure 9

)

Product Numbers 

Verify that the appropriate valve rebuild kits are on 
hand for the cylinders that are to be recharged: 

Valve Size 

(in inches) 

Product 

Numbers 

Rebuild Kit 

CPY-35 
CPY-70 

CPY-VSK1 

1-1/2 

CPY-150 
CPY-25 

CPY-VSK1.5 

2-1/2 

CPY-375 
CPY-560 

CPY-VSK2.5 

CPY-1200 

CPY-VSK4 

Warning/Caution Notations 

WARNING: 

 

 

Personal injury or loss of life 
may occur if you do not follow 
the procedures as specified. 

CAUTION: 

 

 

Equipment damage, or loss of 
data may occur if you do not 
follow the procedures as 
specified. 

Required Tools 

 

Strap wrench 

 

Spanner wrench 

 

WD-40 (or similar) 

 

Silicone RTV sealant 

 

SINX 16, 17, or 18 for respective size 

 

Torque wrench with 3/8" drive 

 

Figure 1. 

Prerequisites 

Verify that there is a sufficient quantity of HFC227ea 
in inventory to complete the entire recharge of each 
cylinder. 

 

Figure 2. 

 

WARNING: 

 

Although the pressure gauge may register a 
“Zero” reading, caution must be used at all 
times since residual pressure may still be 
present. 

 

CAUTION: 

 

Before beginning this procedure, make sure 
the Anti-Recoil Device is installed on the 
cylinder. 

Disassembling the Valve 

1. 

Energize the solenoid or depress a Local 
Manual Control (CPY-LMC) to ensure there is 
no pressure in the cylinder. It is normal to notice 
a slight pressure release. 

At this point, THERE 

IS NO PRESSURE IN THE CYLINDER. 

 

 

Figure 3.

 

Содержание SINORIX CPY-35

Страница 1: ... occur if you do not follow the procedures as specified CAUTION Equipment damage or loss of data may occur if you do not follow the procedures as specified Required Tools Strap wrench Spanner wrench WD 40 or similar Silicone RTV sealant SINX 16 17 or 18 for respective size Torque wrench with 3 8 drive Figure 1 Prerequisites Verify that there is a sufficient quantity of HFC227ea in inventory to com...

Страница 2: ...ure 5 4 Place the valve assembly into a bench mounted vice with rubber inserts or heavy canvas over the teeth of the vise Do not scratch the valve surface 5 Remove the top plug adapter using a spanner wrench Figure 6 NOTE 1 The top plug adapter unscrews with a right hand thread 2 There is a spring under the top plug adapter that will push up the top plug once the threads are disengaged Figure 7 Re...

Страница 3: ...eful not to lose the steel ball under the nut Figure 12 d Remove the rubber seat from the bottom of the piston by unscrewing the retaining clamp using SINX16 17 or 18 to respective size Figure 13 e Remove the O ring from the top of the piston Figure 14 Reassembling the Valve 1 Reassemble the piston NOTE See Product Numbers for valve rebuild kits Figure 15 a Reassemble the piston using new O rings ...

Страница 4: ... size Use a torque wrench with a 3 8 drive Set to proper torque setting Valve Size Seat Retainer in inches Torque IN LBS 1 110 1 5 140 2 5 160 4 400 Figure 19 b Reassemble the valve c Reinstall the valve body to the cylinder if needed Tighten until a metal to metal fit is achieved d Assemble the piston to the valve body Make sure to install the piston with the rubber seat leading into the bottom o...

Страница 5: ...er to the discharge port of the cylinder Figure 24 a Before placing the cylinder reset the scale to 0 b Record the Empty Cylinder Weight c Connect the Fill Manifold to the Fill Adapter Figure 25 d Press the Tare button on the digital scale This will set the display to 0 without resetting the Gross Weight If not using a digital scale record the weight of the cylinder with the Fill Manifold connecte...

Страница 6: ...his indicates the valve did not reseat properly If this occurs i Connect an adapter to the discharge port on the solenoid ii With the Filling Manifold still connected to the Fill Adapter on the cylinder energize the solenoid with the correct voltage to open the solenoid iii Apply 450 psi of Nitrogen for 10 seconds iv Turn off the power to the solenoid v Repeat step m vi Close the valve on the nitr...

Отзывы: