2. 

Remove the brass valve from the cylinder by 
unscrewing from the cylinder neck. Remove the 
valve and the siphon tube assembly and set 
aside.   

 

CAUTION: 

 

Do NOT use a pipe wrench as this will 
scratch the valve. Use a strap wrench or 
attach a piece of pipe to the outlet for 
leverage. 

 

Figure 4. 

3. 

Remove the siphon tube assembly from the 
valve. 

 

Figure 5. 

4. 

Place the valve assembly into a bench-mounted 
vice with rubber inserts or heavy canvas over 
the teeth of the vise.

 

(Do not scratch the valve 

surface.) 

5. 

Remove the top plug adapter using a spanner 
wrench. 

 

Figure 6. 

 

NOTE:

 

1. The top plug adapter unscrews with 
 

a right-hand thread. 

 

2.  There is a spring under the top plug 
 

adapter that will push up the top  

 

plug once the threads are  

 

disengaged. 

 

Figure 7. 

 

Remove the O-ring from the top plug 
adapter. 

 

Figure 8. 

6.  Remove the piston from the inside of the valve 

body. 

 

Figure 9.

 

 

Clean the interior surface of the valve body 

utilizing a product like WD-40, removing all 
of the residual O-ring lube. 

Содержание SINORIX CPY-35

Страница 1: ... occur if you do not follow the procedures as specified CAUTION Equipment damage or loss of data may occur if you do not follow the procedures as specified Required Tools Strap wrench Spanner wrench WD 40 or similar Silicone RTV sealant SINX 16 17 or 18 for respective size Torque wrench with 3 8 drive Figure 1 Prerequisites Verify that there is a sufficient quantity of HFC227ea in inventory to com...

Страница 2: ...ure 5 4 Place the valve assembly into a bench mounted vice with rubber inserts or heavy canvas over the teeth of the vise Do not scratch the valve surface 5 Remove the top plug adapter using a spanner wrench Figure 6 NOTE 1 The top plug adapter unscrews with a right hand thread 2 There is a spring under the top plug adapter that will push up the top plug once the threads are disengaged Figure 7 Re...

Страница 3: ...eful not to lose the steel ball under the nut Figure 12 d Remove the rubber seat from the bottom of the piston by unscrewing the retaining clamp using SINX16 17 or 18 to respective size Figure 13 e Remove the O ring from the top of the piston Figure 14 Reassembling the Valve 1 Reassemble the piston NOTE See Product Numbers for valve rebuild kits Figure 15 a Reassemble the piston using new O rings ...

Страница 4: ... size Use a torque wrench with a 3 8 drive Set to proper torque setting Valve Size Seat Retainer in inches Torque IN LBS 1 110 1 5 140 2 5 160 4 400 Figure 19 b Reassemble the valve c Reinstall the valve body to the cylinder if needed Tighten until a metal to metal fit is achieved d Assemble the piston to the valve body Make sure to install the piston with the rubber seat leading into the bottom o...

Страница 5: ...er to the discharge port of the cylinder Figure 24 a Before placing the cylinder reset the scale to 0 b Record the Empty Cylinder Weight c Connect the Fill Manifold to the Fill Adapter Figure 25 d Press the Tare button on the digital scale This will set the display to 0 without resetting the Gross Weight If not using a digital scale record the weight of the cylinder with the Fill Manifold connecte...

Страница 6: ...his indicates the valve did not reseat properly If this occurs i Connect an adapter to the discharge port on the solenoid ii With the Filling Manifold still connected to the Fill Adapter on the cylinder energize the solenoid with the correct voltage to open the solenoid iii Apply 450 psi of Nitrogen for 10 seconds iv Turn off the power to the solenoid v Repeat step m vi Close the valve on the nitr...

Отзывы: