Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
134
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
Caution:
The input of rating plate data must correspond with the wiring of the motor (star / delta). This means, if
delta wiring is used for the motor, delta rating plate data has to be entered.
,(&0RWRU
'HOWDFRQQHFWLRQ
6WDUFRQQHFWLRQ
:
8
8
9
9
:
:
8
8
9
9
:
8
9
:
8
9
:
Note:
Following diagram shows a typical rating plate with the locations of the relevant motor data.
P0305[0...2] Rated motor current [A] 0.01 -
10000.00
1.86
C(1)
-
DDS
Float 1
Nominal motor current from rating plate.
Dependency: Changeable only when P0010 = 1 (quick commissioning).
Depends also on P0320 (motor magnetization current).
Note:
The maximum value of P0305 depends on the maximum inverter current r0209 and the motor type:
Asynchronous motor : P0305_max = P0209
It is recommended that the ratio of P0305 (rated motor current) and r0207 (rated inverter current) should
not be lower than: (1 / 8) <= (P0305 / r0207)
When the relation of the nominal motor current P0305 and half of the maximal inverter current (r0209)
exceeds 1.5 an additional current derating is applied. This is necessary to protect the inverter from
harmonic current waves.
I
max,Inv
r0209
r0209
P0305
2
⋅
r0209
0.7
⋅
1.5
2.5
Default value is depending on inverter type and its rating data.
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...