Parameter
Value
Adjustment range
p4078[0]
Analog outputs, characteristic value y1
-20.000 to +20.000 V or mA
Factory setting: 0.000 mA
Setting for the y coordinate in V or mA of the first point on the scaling characteristic.
When analog output 0 is set as a voltage output (p4076[0] = 1 / 4) and terminals X522: 3,2 are used, the
unit is V.
When analog output 0 is set as a current output (p4356[0] = 0 / 2 / 3) and terminals X522: 1,2 are used,
the unit is mA.
Parameter
Value
Adjustment range
p4079[0]
Analog outputs, characteristic value x2
-1000.00 to +1000.00%
Factory setting: 100.00 %
Setting for the x coordinate in % of the second point on the scaling characteristic.
Parameter
Value
Adjustment range
p4080[0]
y2 of the characteristic of the analog out‐
puts
-20.000 to +20.000 V or mA
Factory setting: 20.000 mA
Setting for the y coordinate in V or mA of the second point on the scaling characteristic.
When analog output 0 is set as a voltage output (p4076[0] = 1 / 4) and terminals X522: 3,2 are used, the
unit is V.
When analog output 0 is set as a current output (p4356[0] = 0 / 2 / 3) and terminals X522: 1,2 are used,
the unit is mA.
Additional setting parameters for analog output 1 (AO1)
Parameter
Value
Adjustment range
p4077[1]
Analog outputs, characteristic value x1
-1000.00 to +1000.00%
Factory setting: 0.00 %
Setting for the x coordinate in % of the first point on the scaling characteristic.
Operation
8.5 Functions
SINAMICS SM150 6SL3845-2NN41-8AD0
114
Operating Instructions Rev.201908010908 EXAMPLE
Содержание Sinamics SM150 6SL3845-2NN41-8AD0
Страница 2: ...01 08 2019 09 08 V32 00 ...
Страница 98: ...Start up SINAMICS SM150 6SL3845 2NN41 8AD0 98 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 172: ...Spare parts SINAMICS SM150 6SL3845 2NN41 8AD0 172 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 176: ...Service Support SINAMICS SM150 6SL3845 2NN41 8AD0 176 Operating Instructions Rev 201908010908 EXAMPLE ...
Страница 187: ......
Страница 190: ......
Страница 192: ......