5. Fix the power cables from behind to the front. The connection busbars are labeled with the
phase designation.
6. Seal the floor panel and the cables passing through the panel so that they are air-tight.
NOTICE
Damage caused by overheating
Unless the floor panel is air-tight, adequate cooling cannot be guaranteed. This can cause
components to overheat.
● Seal any access holes made in the floor panel immediately after installation so that they
are air tight, in order to ensure sufficient cooling.
6.5.2
Connecting the signal cables
There are terminal strips and interfaces on the Power Stack Adapter in the electronics
compartment of the power unit. The signal traffic to the open-loop and closed-loop control
cabinet is handled via these interchange points.
The terminal blocks are used to wire up the following:
● Signals
● Auxiliary voltage for fans and anti-condensation heating systems
● Power supply for the electronics
Procedure
To connect the signal lines, proceed as follows:
1. Connect the signal lines at the intended clamping points.
2. Connect the shield to the shield bus as shown under Using the equipotential bonding strip
and shield bus (Page 64). Refer to the "Circuit manual for power unit" for the precise
assignment. Pay attention to the EMC directives.
6.5.3
Connect the coupling unit to the evaluation unit
The coupling unit is installed in the power unit at the factory and connected to the correct
terminal.
Electrical connection
6.5 Connecting the power unit
SINAMICS SL150 6SL38600UL432AA0Z
66
Operating Instructions Rev.201910281433 EXAMPLE
Содержание SINAMICS SL150
Страница 2: ...28 10 2019 14 33 V18 00 ...
Страница 10: ...Table of contents SINAMICS SL150 6SL38600UL432AA0Z 10 Operating Instructions Rev 201910281433 EXAMPLE ...
Страница 70: ...Commissioning SINAMICS SL150 6SL38600UL432AA0Z 70 Operating Instructions Rev 201910281433 EXAMPLE ...
Страница 104: ...Spare parts SINAMICS SL150 6SL38600UL432AA0Z 104 Operating Instructions Rev 201910281433 EXAMPLE ...
Страница 116: ...Index SINAMICS SL150 6SL38600UL432AA0Z 116 Operating Instructions Rev 201910281433 EXAMPLE ...
Страница 117: ......
Страница 120: ......
Страница 122: ......