STW1 (control word 1)
See function diagram [2442].
Table 10- 8 Control word 1 (STW1)
Bit
Meaning
Explanation
Operating
condition
BICO
0
0 = OFF1 (OFF1)
0: Deceleration on the down ramp, then pulse
inhibit, line contactor (if present) is opened
1
BI: p0840
0
→
1 = ON
Pulse enable possible
1
0 = Coast down (OFF2)
0: Pulse inhibit, line contactor (if present) is
opened
1
BI: p0844
BI: p0845
1 = Do not coast down
Enable possible
Note: Control signal OFF2 is generated by ANDing BI: p0844 and BI: p0845.
2
0 = Quick stop (OFF3)
0: Deceleration on the quick stop ramp, then
pulse inhibit, line contactor (if present) is opened.
1
BI: p0848
1 = No quick stop
Enable possible
Note: Control signal OFF3 is generated by ANDing BI: p0848 and BI: p0849.
3
0 = Inhibit operation
0: Pulse inhibit. The motor coasts down. The
"Ready for Operation" state remains set.
1
BI: p0852
1 = Enable operation
1: Pulse enable, ramp-up with active setpoint
4
0 = Inhibit ramp-function
generator
0: The ramp-function generator output is set to
setpoint "0".
1
BI: p1140
1 = Enable ramp-function
generator
5
0 = Stop ramp-function
generator
0: The current setpoint is frozen at the ramp-
function generator output.
1
BI: p1141
1 = Start ramp-function
generator
6
1 = Enable speed setpoint
1: The speed setpoint at the input of the ramp-
function generator is enabled.
1
BI: p1142
0 = Inhibit speed setpoint
0: The speed setpoint at the input of the ramp-
function generator is set to zero. The drive
brakes in accordance with the set ramp-down
time.
7
0
→
1 = Acknowledge fault
A positive edge change acknowledges all the
current faults.
-
BI: p2103
Note: Acknowledgement is realized with a 0/1 edge via BI: p2103 or BI: p2104 or BI: p2105.
8
Reserved
-
-
9
Reserved
-
-
10
1 = Control via PLC
1: PROFIBUS control words and setpoints are
analyzed.
1
BI: p0854
0: PROFIBUS control words and setpoints are
not analyzed.
Note: This bit should not be set to "1" until the PROFIBUS slave has returned an appropriate status via ZSW1.9