Functions, monitoring and protective functions
9.5 Monitoring functions and protective functions
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
711
Selection of sensor types
●
p4100[0...11] sets the sensor type for the respective temperature channel.
●
r4105[0...11] indicates the actual value of the temperature channel.
For switching temperature sensors, such as PTC and bimetallic NC contact, two limits are
displayed symbolically:
–
r4105[0...11] = -58 °F (-50 °C): The actual temperature value is below the rated
response temperature.
–
r4105[0...11] = +482 °F (+250 °C): The actual temperature value is above the rated
response temperature.
Note
PTC and bimetallic NC contact
The value indicated in r4105[0...11] does not correspond to the actual temperature value.
Table 9- 21 Selection of sensor types
Value of p4100[0...11] Temperature sensor
Temperature display range r4105[0...11]
0
Evaluation disabled
-
1
PTC thermistor
-58 °F (-50 °C) or +482 °C (+250 °C)
2
KTY84
-146.2 °F (-99 °C) to +482 °F (+250 °C)
4
Bimetallic NC contact
-58 °F (-50 °C) or +482 °C (+250 °C)
5
PT100
-146.2 °F (-99 °C) to +482 °F (+250 °C)
6
PT1000
-146.2 °F (-99 °C) to +482 °F (+250 °C)
Measurement of cable resistances
When using 2-wire sensors (1x2, 2x2-wire systems), to increase the measuring accuracy,
the cable resistance can be measured and saved.
Procedure for determining the cable resistance:
1.
Select the measuring method (1x2/2x2) for the corresponding terminal block
(p4108[0...5] = 0, 1).
2.
Set the required sensor type for the relevant channel (p4100[x] = 1 ... 6, x = 0...5
or 0...11).
3.
Jumper the sensor to be connected (short-circuit the sensor cable in the vicinity of the
sensor).
4.
Connect the sensor cables to the relevant terminals 1(+), 2(-) or 3(+), 4(-).
5.
Start measurement of the cable resistance (p4109[x] = 1) for the relevant channel.
6.
After p4109[x] = 0, check the measured resistance value in p4110[x].
7.
Remove jumper across the temperature sensor again.
Содержание SINAMICS S150 NEMA
Страница 1: ......
Страница 2: ......
Страница 20: ...Table of contents Enclosed Drives 18 Operating Instructions 12 2018 A5E36652151A ...
Страница 42: ...Device overview 2 5 Rating plate Enclosed Drives 40 Operating Instructions 12 2018 A5E36652151A ...
Страница 200: ...Electrical installation 4 9 Additional connections Enclosed Drives 198 Operating Instructions 12 2018 A5E36652151A ...
Страница 500: ...Output terminals 8 3 Digital outputs Enclosed Drives 498 Operating Instructions 12 2018 A5E36652151A ...
Страница 828: ...Technical specifications 12 3 Technical specifications Enclosed Drives 826 Operating Instructions 12 2018 A5E36652151A ...
Страница 861: ......
Страница 862: ......