Infeed
2.1 Active Infeed
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
31
2.1.1
Active Infeed closed-loop control booksize
Figure 2-1
Schematic structure of Active Infeed booksize
Active Infeed closed-loop control for Active Line Modules booksize
The Active Line Module can be operated in two different modes depending on the
parameterized line supply voltage (p0210):
●
Active Mode
In the Active Mode, the DC link voltage is regulated to a variable setpoint (p3510) which
results in a sinusoidal line current (cos
φ = 1). The level of the reactive current is also
controlled and can be specifically defined.
●
Smart Mode
Energy recovery capability is maintained in Smart Mode, although there is a lower DC link
voltage in comparison to the Active Mode. The DC link voltage is dependent on the
current line voltage.
The Extended Smart Mode can be activated as an option (see Chapter "Extended Smart
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......