Basic information about the drive system
13.12 System rules, sampling times and DRIVE-CLiQ wiring
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
1011
13.12.3.3
Default settings for the sampling times
The sampling times of the functions are pre-assigned automatically when the drive is
configured.
These default settings are based on the selected mode (vector/servo control) and the
activated functions.
If isochronous mode is to be possible with a controller, before the automatic configuration,
parameter p0092 must be set to "1" in order that the sampling times are appropriately preset.
If isochronous operation is not possible due to incorrect sampling time settings, an
appropriate message will be output (A01223, A01224).
If the application requires a change of the preset sampling times, they can be set using
parameters p0112 and p0113 or directly using p0115, p0799 and p4099.
Note
Recommendation
Only appropriately qualified experts should change the sampling times set as default values.
When commissioning for the first time, the current controller sampling times (p0115[0]) are
automatically preset with factory setting values:
Table 13- 11 Factory settings
Construction type
Number
p0112
p0115[0]
p1800
Active Infeed
Booksize
1
2 (Low)
250 µs
-
Chassis
400
V / ≤ 300
kW
690
V / ≤ 330
kW
1
1
2 (Low)
2 (Low)
250 µs
250 µs
-
-
Chassis
400 V / > 300 kW
690 V / > 330 kW
1
1
0 (Expert)
1 (xLow)
375 µs (p0092 =
1)
400 µs (p0092 =
0)
-
-
Smart Infeed
Booksize
1
2 (Low)
250 µs
-
Chassis
400
V / ≤ 355
kW
690
V / ≤ 450
kW
1
1
2 (Low)
2 (Low)
250 µs
250 µs
-
-
Chassis
400 V / > 355 kW
690 V / > 450 kW
1
1
0 (Expert)
1 (xLow)
375 µs (p0092 =
1)
400 µs (p0092 =
0)
-
-
Basic Infeed
Booksize
1
4 (High)
250 µs
-
Chassis
1
2 (Low)
2000 µs
-
SERVO
Содержание SINAMICS S120
Страница 1: ......
Страница 2: ......
Страница 24: ...Contents Drive functions 24 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 202: ...Servo control 4 21 Voltage precontrol Drive functions 202 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 296: ...Vector control 5 23 Asynchronous pulse frequency Drive functions 296 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 312: ...V f control vector control 6 5 Vdc control Drive functions 312 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 932: ......
Страница 1044: ...Appendix A 2 Documentation overview Drive functions 1044 Function Manual 11 2017 6SL3097 4AB00 0BP5 A 2 Documentation overview ...
Страница 1082: ...Appendix A 7 Functions of SINAMICS S120 Combi Drive functions 1082 Function Manual 11 2017 6SL3097 4AB00 0BP5 ...
Страница 1094: ......