Speed Derate Curve Menu (1151) Parameters*
Parameter
ID
Unit
Default
Min
Max
Description
0 Percent Break
Point
1152
%
0.0
0.0
200.0
Set the maximum motor load at 0% speed.
10 Percent Break
Point
1153
%
31.6
0.0
200.0
Set the maximum motor load at 10% speed.
17 Percent Break
Point
1154
%
41.2
0.0
200.0
Set the maximum motor load at 17% speed.
25 Percent Break
Point
1155
%
50.0
0.0
200.0
Set the maximum motor load at 25% speed.
50 Percent Break
Point
1156
%
70.7
0.0
200.0
Set the maximum motor load at 50% speed.
100 Percent Break
Point
1157
%
100.0
0.0
200.0
Set the maximum motor load at 100%
speed.
* The parameters in this table are used to set the inverse time TOL algorithm for speed de‐
rating, in parameter Overload select (1130).
Table 6-5
Auto-tune Menu (1260) Parameters
Parameter ID
Type
Default
Description
Auto-tune
stage 1
1260
Function
This function determines the stator resistance and leakage inductance
of the motor. The motor does not rotate during this stage. If this func‐
tion is not used the menu-entered values are used. If the function is
used, the parameters will be updated with the calculated values.
Auto-tune
stage 2
1270
Function
This function determines the no-load current and rotor inertia of the
motor. The motor rotates during this stage. If this function is not used
the menu entered values are used. Only use this function in special
circumstances requiring high response rates.
Parameter Assignment/Addressing
6.3 Options for Motor Menu (1) - first half
Control Manual
Operating Manual, A5E50491925A
95
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...