Drive output rebalanced by bypassing functional cells (not using neutral shift)
One solution is to bypass an equal number of cells in all three phases, even though some may
not have failed. This method prevents imbalance but sacrifices voltage capability. The example
below shows a 15 cell drive after bypass of two cells in all phases to restore balance. 87% of the
cells are functional but only 60% are in use, and only 60% of full voltage is available.
&
%
$
9%$
9$&
9&%
$
$
$
&
%
1
&
%
&
%
r
7<3
Figure 7-5
Drive Output rebalanced by bypassing functional cells
Drive output re-balanced by adjusting phase angles (neutral shift)
A better approach is using neutral shift. This method takes advantage of the fact that the star-
point of the cells is floating, and is not connected to the neutral of the motor.
Neutral shift:
• shifts the star-point of cells away from the motor neutral
• adjusts the phase angles of the cell voltages
• helps to obtain a balanced set of motor voltages even though the cell group voltages are not
balanced.
This approach is equivalent to introducing a zero-sequence component into the voltage
command vectors for the cells.
The example shows a 15 cell drive after bypass of two cells in phase A only. Neutral shift adjusts
the phase angles of the cell voltages so that phase A is displaced from phase B and from phase
C by 132.5°, instead of the normal 120°. 87% of the functional cells are in use, and 80% of full
voltage is available.
Operating the Control
7.4 Cell Bypass
Control Manual
Operating Manual, A5E50491925A
187
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...