Functions, monitoring, and protective functions
9.2 Drive functions
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
477
WARNING
Danger to life if the motor unexpectedly moves during motor identification in the rotating
mode
When selecting motor identification with optimization in the rotating mode, after
commissioning, the drive initiates that the motor rotates with speeds that can reach the
maximum motor speed.
•
Observe the general safety instructions.
•
Ensure that the EMERGENCY STOP functions are fully functional when commissioning
the drive.
9.2.1.1
Motor data identification
Description
Motor identification with p1910 is used for determining the motor parameters at standstill
(see also p1960: speed controller optimization):
●
Equivalent circuit diagram data p1910 = 1
●
Magnetization characteristic p1910 = 3
For control engineering reasons, you are strongly advised to carry out motor identification
because the equivalent circuit diagram data, motor cable resistance, IGBT on-state voltage,
and compensation for the IGBT lockout time can only be estimated if the data on the type
plate is used. For this reason, the stator resistance for the stability of sensorless vector
control or for the voltage boost with the V/f characteristic is very important.
Motor identification is essential if long supply cables or third-party motors are used. When
motor data identification is started for the first time, the following data is determined with
p1910 = 1 on the basis of the data on the type plate (rated data):
Table 9- 1
Data determined using p1910
Induction motor
Permanent-magnet synchronous motor
p1910 = 1
•
Stator resistance (p0350)
•
Rotor resistance (p0354)
•
Stator leakage inductance (p0356)
•
Rotor leakage inductance (p0358)
•
Magnetizing inductance (p0360)
•
Drive converter valve threshold voltage (p1825)
•
Converter valve interlocking times (p1828 ...
p1830)
•
Stator resistance (p0350)
•
Stator resistance q axis (p0356)
•
Stator inductance d axis (p0357)
•
Drive converter valve threshold voltage
(p1825)
•
Converter valve interlocking times (p1828 ...
p1830)
p1910 = 3
•
Saturation characteristics (p0362 ... p0366)
not recommended
Notice: When encoder adjustment is complete,
the motor is automatically rotated approx. one
revolution in order to determine the zero marker
of the encoder.
Содержание SINAMICS G150
Страница 1: ......
Страница 2: ......
Страница 8: ...Foreword Converter cabinet units 8 Operating Instructions 07 2016 A5E03347396A ...
Страница 18: ...Table of contents Converter cabinet units 18 Operating Instructions 07 2016 A5E03347396A ...
Страница 38: ...Device overview 2 5 Type plate Converter cabinet units 38 Operating Instructions 07 2016 A5E03347396A ...
Страница 679: ......
Страница 680: ......