Description:
Sets the threshold value for instaneous switching-in or switching-out motors.
Note
If the PID error rises above the multi-pump control overcontrol threshold p29526, the converter skips the switch-in delay
time and performs the switch-in operation immediately.
If the PID error drops below the multi-pump control overcontrol threshold -p29526, the converter skips the switch-out
delay and performs the switch-out operation immediately.
p29527
Multi-pump control interlocking time / Mpc t_interl
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [s]
Max:
650 [s]
Factory setting:
0 [s]
Description:
Interlocking time during which, following the connection or disconnection of a motor, no further motors are connected
or disconnected using the multi-control control. This avoids duplicate switching operations.
p29528
Multi-pump control switch-out speed offset / Mpc sw_out offset
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: -
Min:
0.0 [rpm]
Max:
21000.0 [rpm]
Factory setting:
100.0 [rpm]
Description:
Sets the speed offset which pluses p1080 as the speed threshold.
If the system deviation of the technology controller has exceeded the threshold p29523 for p29525s (or exceeded the
threshold p29526) and the motor has reached the speed threshold p1080+p29528, a motor will be switched out.
r29529.0...19
CO/BO: Multi-pump control status word / Mpc ZSW
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status word of the multi-pump control
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Start motor 1
Yes
No
-
01
Start motor 2
Yes
No
-
02
Start motor 3
Yes
No
-
03
Start motor 4
Yes
No
-
04
Start motor 5
Yes
No
-
05
Start motor 6
Yes
No
-
06
Reserved
-
07
Reserved
-
08
Reserved
-
09
Reserved
-
10
Reserved
-
11
Reserved
-
12
Reserved
-
13
Reserved
-
14
Reserved
-
15
Reserved
-
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
917
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......