Note
When the "hibernation mode" function (p2398 = 1) is activated, its behavior is defined as to whether the technology
controller is additionally switched in (closed-loop) or switched out (open-loop).
The technology controller is enabled via binector input p2200 and its mode is set in p2251.
p2200 = 0, p2251 = 0:
Hibernation mode operates without technology controller (open-loop)
p2200 = 1, p2251 = 0:
Hibernation mode operates with technology controller (closed-loop)
r2399.0...8
CO/BO: Hibernation mode status words / Hib ZSW
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7038
Min:
-
Max:
-
Factory setting:
-
Description:
Display and BICO output for the status word of the "hibernation mode" function.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Hibernation mode enabled (p2398 <> 0)
Yes
No
-
01
Hibernation mode active
Yes
No
-
02
Hibernation mode delay active
Yes
No
-
03
Hibernation boost active
Yes
No
-
04
Hibernation mode motor switched off
Yes
No
-
05
Hibernation mode switched off cyclic restart active
Yes
No
-
06
Hibernation motor motor restarts
Yes
No
-
07
Hibernation mode supplies total setpoint for ramp-fct
generator
Yes
No
-
08
Hibernation mode bypasses ramp-fct generator in setpoint
channel
Yes
No
-
Dependency:
See also: p2398
See also: A07325
p2900[0...n]
CO: Fixed value 1 [%] / Fixed value 1 [%]
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 1021
Min:
-10000.00 [%]
Max:
10000.00 [%]
Factory setting:
0.00 [%]
Description:
Setting and connector output for a fixed percentage value.
Dependency:
See also: p2901, r2902, p2930
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note
The value can be used to interconnect a scaling function (e.g. scaling the main setpoint).
Parameters
7.2 Parameter list
SINAMICS G120X converter
824
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......