Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
|n_act| < speed threshold value 3
Yes
No
8010
01
f or n comparison value reached or exceeded
Yes
No
8010
04
Speed setpoint - actual value deviation in tolerance t_on
Yes
No
8011
05
Ramp-up/ramp-down completed
Yes
No
8011
Note
For bit 00:
The speed threshold value 3 is set in p2161.
For bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit is not reset.
p2200[0...n]
BI: Technology controller enable / Tec_ctrl enable
Access level: 2
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to switch in/switch out the technology controller.
The technology controller is switched in with a 1 signal.
p2201[0...n]
CO: Technology controller fixed value 1 / Tec_ctrl fix val1
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: DDS, p0180
Unit group: 9_1
Unit selection: p0595
Function diagram: 7950, 7951
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
10.00 [%]
Description:
Sets the value for fixed value 1 of the technology controller.
Dependency:
See also: p2220, p2221, p2222, p2223, r2224, r2229
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2202[0...n]
CO: Technology controller fixed value 2 / Tec_ctr fix val 2
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: DDS, p0180
Unit group: 9_1
Unit selection: p0595
Function diagram: 7950, 7951
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
20.00 [%]
Description:
Sets the value for fixed value 2 of the technology controller.
Dependency:
See also: p2220, p2221, p2222, p2223, r2224, r2229
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
791
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......