r0021
CO: Actual speed smoothed / Actual speed
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 6799
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Displays the calculated and smoothed rotor speed.
Frequency components from the slip compensation (for induction motors) are not included.
Dependency:
See also: r0022, r0063
Note
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
r0022
Actual speed rpm smoothed / Actual speed
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6799
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Displays the calculated and smoothed rotor speed.
Frequency components from the slip compensation (for induction motors) are not included.
r0022 is identical to r0021, however, it always has units of rpm and contrary to r0021 cannot be changed over.
Dependency:
See also: r0021, r0063
Note
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The speed actual value is available smoothed (r0021, r0022) and unsmoothed (r0063).
r0024
Output frequency smoothed / Output frequency
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 6300, 6799
Min:
- [Hz]
Max:
- [Hz]
Factory setting:
- [Hz]
Description:
Displays the smoothed output frequency.
Frequency components from the slip compensation (for induction motors) are included.
Dependency:
See also: r0066
Note
Smoothing time constant = 100 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
The output frequency is available smoothed (r0024) and unsmoothed (r0066).
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
473
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......