Parameters
Number
Name
Factory setting
p29631[0...4]
Flow meter pump power
0.00 kW
p29632[0...4]
Flow meter pump flow
0.00 m
3
/h
r29633
Flow meter calculated flow
- m
3
/h
For more information about the parameters, see Chapter "Parameter list (Page 470)".
6.10.8
PROFIenergy
Overview
PROFIenergy is a standard based on PROFINET. PROFIenergy is certified and described in
the PROFIenergy profile of the PNO.
The higher-level controller transfers the control commands and status queries in acyclic
operation via data record 80A0 hex.
The converter supports the PROFIenergy profile V1.1 and the function unit class 3.
The converter supports PROFIenergy energy-saving mode 2.
Function description
Behavior of the converter with active energy-saving mode 2:
● The converter outputs alarm A08800.
● The RDY LED flashes green: 500 ms on, 3000 ms off.
● The converter does not send any diagnostic interrupts.
● If the higher-level controller goes to stop or the bus connection to the higher-level controller
is interrupted, the converter exits the energy-saving mode and resumes normal operation.
Example
You can find an application example for PROFIenergy on the Internet:
PROFIenergy - saving energy with SIMATIC S7 (
support.industry.siemens.com/cs/ww/en/view/41986454
Parameters
Number
Name
Factory setting
r5600
Pe energy-saving mode ID
-
r5613
CO/BO: Pe energy-saving active/inactive
-
Advanced commissioning
6.10 Energy saving
SINAMICS G120X converter
456
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......