6.3.2.4
Analog inputs
Function description
,
8
,
8
,
S>@
$,
$,
U>@
&,S\\\\
S>@
$,
$,
U>@
&,S\\\\
S>@
$,
U>@
&,S\\\\
S>@
$,
*1'
U>@
&,S\\\\
˽
˽
7(03
7(03
1)
with I/O Extension Module
Define the analog input type
The parameter p0756[x] and the switch on the converter specify the analog input type.
Table 6-4
Default settings via parameter p0756
AI 0 Unipolar voltage input
0 V … +10 V
p0756[0] = 0
Unipolar voltage input monitored
+2 V … +10 V
1
Unipolar current input
0 mA … +20 mA
2
Unipolar current input monitored
+4 mA … +20 mA
3
Bipolar voltage input (factory setting)
‑10 V … +10 V
4
AI 1 Unipolar voltage input
0 V … +10 V
p0756[1] = 0
Unipolar voltage input monitored
+2 V … +10 V
1
Unipolar current input
0 mA … +20 mA
2
Unipolar current input monitored
+4 mA … +20 mA
3
Bipolar voltage input (factory setting)
‑10 V … +10 V
4
AI 2 Unipolar current input (factory setting)
0 mA … +20 mA
p0756[2] = 2
Unipolar current input monitored
+4 mA … +20 mA
3
LG-Ni1000 temperature sensor
6
Pt1000 temperature sensor
7
No sensor connected
8
DIN-Ni1000 temperature sensor (6180 ppm / K)
10
AI 3 LG-Ni1000 temperature sensor
p0756[3] = 6
Pt1000 temperature sensor
7
No sensor connected (factory setting)
8
DIN-Ni1000 temperature sensor (6180 ppm / K)
10
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
196
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
Содержание SINAMICS G120X
Страница 2: ......
Страница 152: ...Wiring 4 2 Control interfaces SINAMICS G120X converter 150 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 940: ...Parameters 7 3 ASCII table SINAMICS G120X converter 938 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1114: ...Appendix A 1 Manuals and technical support SINAMICS G120X converter 1112 Operating Instructions 06 2019 FW V1 01 A5E44751209B AC ...
Страница 1147: ......