Functions
7.4 Setpoint calculation
Inverter cabinet units
352
Operating Instructions, 12/2014, A5E32923362A
7.4.6
Speed limitation
The maximum speed limits the speed
setpoint range for both directions of
rotation.
The inverter generates a message
(fault or alarm) when the maximum
speed is exceeded.
If you must limit the speed depending on the direction of rotation, then you can define speed
limits for each direction.
Table 7- 19 Parameters for the speed limitation
Parameter
Description
p1082
Maximum speed, pre-assigned for the automatic calculation of the control parameters
p1083
Speed limit, positive direction of rotation (factory setting: 210000 rpm)
p1085
CI: Speed limit, positive direction of rotation (factory setting: p1083)
p1086
Speed limit, negative direction of rotation (factory setting: -210000 rpm)
p1088
CI: Speed limit, negative direction of rotation (factory setting: p1086)
7.4.7
Ramp-function generator
The ramp-function generator in the setpoint channel limits the rate that the speed setpoint
changes. As a consequence the motor accelerates and brakes more softly, reducing the
stress on the mechanical system of the driven machine.
The ramp-function generator is not active if the technology closed-loop controller in the
inverter specifies the speed setpoint.
Simple ramp-function generator
This inverter always uses the extended ramp-function generator. Consequently, the simple
ramp-function generator is not described in this manual.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......