Operation
6.3 Communication via PROFINET
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
179
6.3.2
Connect the converter to PROFINET
Connecting up
Connect the inverter (IO device) and your PG/PC (IO supervisor) via PROFINET cables with
the control. The maximum permissible cable length is 100 m.
See also Section: CU230P-2 PN Control Unit (option K96) (Page 72).
Figure 6-5
Example: PROFINET in a line topology
Recommended PROFINET connectors and pin assignment
We recommend the following connector with article number: 6GK1901-1BB10-2Ax0 for
connecting the PROFINET cable.
Instructions for assembling the SIMATIC NET Industrial Ethernet FastConnect RF45 Plug
180 can be found on the Internet under product information "Assembly instructions for
SIMATIC NET Industrial Ethernet FastConnect RJ45 Plug
http://support.automation.siemens.com/WW/view/en/37217116/133300
Laying and shielding the PROFINET cable
Information can be found on the Internet: PROFIBUS user organization installation
guidelines (
http://www.profibus.com/downloads/installation-guide/
6.3.3
Configuring communication to the control
Loading GSDML
In order to establish communication between the inverter and controller via PROFINET, you
need the device file of the inverter "GSDML" for your controller. You can then configure the
communication.
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......