Operation
6.3 Communication via PROFINET
Inverter cabinet units
178
Operating Instructions, 12/2014, A5E32923362A
6.3
Communication via PROFINET
The Control Unit provides the following functions:
•
IRT without isochronous mode
•
MRP
Media redundancy, not bumpless with 200 ms
Precondition: Ring topology
•
MRPD
Media redundancy, bumpless
Precondition: IRT and the ring topology created in the
control
•
Diagnostic alarms
According to error classes specified in the PROFIdrive
profile. See Activating diagnostics via the control
(Page 181).
•
Device replacement without
removable data storage medium
Precondition: Topology created in the control
The Control Units have two RJ45 sockets that you can use to implement a line topology. You
can implement all topologies by using switches.
Additional information on PROFINET on the Internet
General information about PROFINET can be found at Industrial Communication
http://www.automation.siemens.com/mcms/automation/en/industrial-
communications/profinet/Pages/Default.aspx
The configuration of the functions is described in the PROFINET system description
http://support.automation.siemens.com/WW/view/en/19292127
) manual.
6.3.1
What do you need for communication via PROFINET?
Check the communication settings using the following table. If you answer "Yes" to the
questions, you have correctly set the communication settings and can control the inverter via
the fieldbus.
Questions
Answer/description
Is the inverter correctly connected to the
PROFINET?
See: Connect the converter to PROFINET
(Page 179)
Do the IP address and device name in the invert-
er and controller match?
See: Configuring communication to the control
(Page 179)
Is the same telegram set in the inverter as in the
higher-level controller?
Set the telegram in the inverter, see: Select tele-
Are the signals that the inverter and the controller
exchange via PROFINET correctly interconnect-
ed?
PROFIdrive-compliant interconnection in the
inverter, see: PROFIdrive profile for PROFIBUS
and PROFINET (Page 186)
Содержание SINAMICS G120P
Страница 1: ......
Страница 2: ......
Страница 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Страница 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Страница 255: ...Operation 6 8 Communication via RS485 Inverter cabinet units Operating Instructions 12 2014 A5E32923362A 255 ...
Страница 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Страница 496: ......