Advanced commissioning
7.2 Inverter control
Converter with control units CU250D-2
124
Operating Instructions, 04/2015, FW V4.7.3, A5E34261542B AB
7.2.4
Switching over the inverter control (command data set)
In some applications, it must be possible to switch over the master control for operating the
inverter.
Example: The motor is to be operable either from a central control via the fieldbus or from a
local control box via the terminal strip.
Command data set (CDS)
This means that you can set the inverter con-
trol in various ways and toggle between the
settings. For instance, as described above,
the inverter can either be operated via a
fieldbus or via the terminal strip.
The settings in the inverter, which are as-
signed to a specific master control, are termed
the command data set.
You select the command data set using parameter p0810. To do this, you must interconnect
parameter p0810 with a control command of your choice, e.g. a digital input.
Figure 7-5
Example for the various command data sets