4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G120D
812
List Manual (LH14), 01/2016, A5E33842313
4.2
List of faults and alarms
Product: SINAMICS G120D, Version: 4707900, Language: eng
Objects: CU240D-2_DP, CU240D-2_DP_F, CU240D-2_PN, CU240D-2_PN_F, CU250D-2_DP_F, CU250D-2_PN_F
F01000
Internal software error
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An internal software error has occurred.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- evaluate fault buffer (r0945).
- carry out a POWER ON (switch-off/switch-on) for all components.
- if required, check the data on the non-volatile memory (e.g. memory card).
- upgrade firmware to later version.
- contact Technical Support.
- replace the Control Unit.
F01001
FloatingPoint exception
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
POWER ON
Cause:
An exception occurred during an operation with the FloatingPoint data type.
The error may be caused by the basic system or an OA application (e.g., FBLOCKS, DCC).
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Note:
Refer to r9999 for further information about this fault.
r9999[0]: Fault number.
r9999[1]: Program counter at the time when the exception occurred.
r9999[2]: Cause of the FloatingPoint exception.
Bit 0 = 1: Operation invalid
Bit 1 = 1: Division by zero
Bit 2 = 1: Overflow
Bit 3 = 1: Underflow
Bit 4 = 1: Inaccurate result
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- check configuration and signals of the blocks in FBLOCKS.
- check configuration and signals of DCC charts.
- upgrade firmware to later version.
- contact Technical Support.
F01002
Internal software error
Message class:
Hardware/software error (1)
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
An internal software error has occurred.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.
Содержание SINAMICS G120D CU240D-2 DP
Страница 1: ...s SINAMICS SINAMICS G120D Control Units CU240D 2 CU250D 2 List Manual 01 2016 Edition ...
Страница 2: ......
Страница 954: ...4 Faults and alarms 4 2 List of faults and alarms SINAMICS G120D 954 List Manual LH14 01 2016 A5E33842313 ...
Страница 978: ...Index SINAMICS G120D 978 List Manual LH14 01 2016 A5E33842313 ...
Страница 979: ......