7.6
Set values for monitoring the winding temperature
Prior to commissioning
Before running the machine for the first time, set the temperature value for shutdown on the
monitoring device.
Table 7-3
Set values for monitoring the winding temperatures during commissioning
Set value
Temperature
Shutdown
145 °C
Normal operation
Measure the normal operating temperature T
operation
at the installation site in °C. Set the values
for shutdown and warning according to the operating temperature T
operation
. The set values
depend on the design of the insulation system or the temperature class of the machine. The
data can be found on the rating plate.
Table 7-4
Set values for monitoring the winding temperatures in normal operation
Set value
Insulation class 155(F)
Insulation class 180(H)
Warning
T
op
+ 10 K ≤ 145 °C
T
op
+ 10 K ≤ 170 °C
Shutdown
T
op
+ 15 K ≤ 155 °C
T
op
+ 15 K ≤ 180 °C
7.7
Test run
After installation or inspection, carry out a test run:
1. Start up the machine without a load. To do this, close the circuit breaker and do not switch
off prematurely. Check whether it is running smoothly.
Switching the machine off again while it is starting up and still running at slow speed should
be kept to a bare minimum, for example for checking the direction of rotation or for checking
in general.
Allow the machine to run down before switching it on again.
2. If the machine is running smoothly and evenly, switch on the cooling equipment. Continue
to observe the machine for a while in no-load operation.
Start-up
7.6 Set values for monitoring the winding temperature
SIMOTICS TN Series N-compact 1LL8
86
Operating Instructions 11/2018
Содержание SIMOTICS TN 1LL8
Страница 2: ...15 11 2018 10 24 V17 00 ...
Страница 12: ...Table of contents SIMOTICS TN Series N compact 1LL8 12 Operating Instructions 11 2018 ...
Страница 26: ...Description SIMOTICS TN Series N compact 1LL8 26 Operating Instructions 11 2018 ...
Страница 62: ...Assembly 5 3 Installing the machine SIMOTICS TN Series N compact 1LL8 62 Operating Instructions 11 2018 ...
Страница 98: ...Operation 8 9 faults SIMOTICS TN Series N compact 1LL8 98 Operating Instructions 11 2018 ...
Страница 132: ...Spare parts 10 14 Terminal box 1XB9600 SIMOTICS TN Series N compact 1LL8 132 Operating Instructions 11 2018 ...
Страница 136: ...Disposal 11 5 Disposal of components SIMOTICS TN Series N compact 1LL8 136 Operating Instructions 11 2018 ...
Страница 138: ...Service and Support SIMOTICS TN Series N compact 1LL8 138 Operating Instructions 11 2018 ...
Страница 142: ...Quality documents SIMOTICS TN Series N compact 1LL8 142 Operating Instructions 11 2018 ...
Страница 147: ......