Converter operation
● If the design of the motor requires connection to a particular converter type, the rating plate
will contain corresponding additional information.
● The converter is correctly parameterized. The parameterization data is specified on the
rating plate of the machine. Information about the parameters is available in the operating
instructions for the converter.
● Any supplementary motor monitoring devices and equipment have been correctly
connected and are functioning correctly.
● In continuous operation, the motor cannot exceed the specified upper speed limit n
max
or
undershoot the lower speed limit n
min
.
The permissible acceleration time to the limit speed n
min
depends on the parameter
assignment.
WARNING
Dangerous voltage via the converter
As long as the feeding converter is switched on, or the DC link of the converter is not
discharged, there can be a voltage at the motor terminals even when the rotor is not moving.
The voltage is up to 1000 V, depending on the converter type.
Ensure that the five safety rules (Page 16) are followed before working on the motor.
7.3
Measuring the insulation resistance before commissioning
Measuring the insulation resistance and polarization index (PI) provides information on the
condition of the machine. It is therefore important to check the insulation resistance and the
polarization index at the following times:
● Before starting up a machine for the first time
● After an extended period in storage or downtime
● Within the scope of maintenance work
The following information is provided regarding the state of the winding insulation:
● Is the winding head insulation conductively contaminated?
● Has the winding insulation absorbed moisture?
As such, you can determine whether the machine needs commissioning or any necessary
measures such as cleaning and/or drying the winding:
● Can the machine be put into operation?
● Must the windings be cleaned or dried?
Detailed information on testing and the limit values can be found here:
"Testing the insulation resistance and polarization index" (Page 61)
Start-up
7.3 Measuring the insulation resistance before commissioning
SIMOTICS FD 1MH1
Operating Instructions 08/2017
107
Содержание SIMOTICS FD 1LL1
Страница 2: ...18 08 2017 17 24 V10 00 ...
Страница 32: ...Description 3 1 Comparison of IEC and GOST standards SIMOTICS FD 1MH1 32 Operating Instructions 08 2017 ...
Страница 58: ...Preparations for use 4 19 Converter operation SIMOTICS FD 1MH1 58 Operating Instructions 08 2017 ...
Страница 104: ...Electrical connection 6 6 Connecting the auxiliary circuits SIMOTICS FD 1MH1 104 Operating Instructions 08 2017 ...
Страница 120: ...Start up 7 10 Setting the motor parameters at the converter SIMOTICS FD 1MH1 120 Operating Instructions 08 2017 ...
Страница 176: ...Disposal 11 4 Disposal of components SIMOTICS FD 1MH1 176 Operating Instructions 08 2017 ...
Страница 178: ...Service and Support SIMOTICS FD 1MH1 178 Operating Instructions 08 2017 ...
Страница 182: ...Quality documents SIMOTICS FD 1MH1 182 Operating Instructions 08 2017 ...
Страница 187: ......