Communication
2.2 PROFINET communication
SIMOCODE pro - Communication
78
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
2.2.16
PROFIenergy
PROFIenergy - definition
PROFIenergy, a protocol defined by the PROFINET User Organization, lays the foundations
for a vendor-neutral, universal system for flexible, short-term, and intelligent shutdown of
individual loads or whole production units.
PROFIenergy - functions supported
With the PROFIenergy data record index 0x80A0, SIMOCODE pro V PN (GP) supports the
following PROFIenergy functions of device class type 3 "Switching and measuring devices
without their own energy-saving level":
Table 2- 28 PROFIenergy - functions supported
Service
Service-ID
Meaning
Start_Pause
0x01
Switching off the motor in "remote" mode
End_Pause
0x02
Possible to switch on the motor again
Query_Modes
- list of modes
- get mode
0x03
Energy-saving modes
- Query the supported energy-saving modes
- Read out the energy-saving mode
PEM_Status
0x04
Read out of the PROFIenergy status
PE_Identify
0x05
Read out of the supported PROFIenergy services
Query_Measurement
- get measurement list
- get measurement values
0x10
Measured values
- Query the list of supported measured values
- Read out the supported measured values
Start_Pause
The "Start_Pause" command result in direct shutdown of the motor and activation of the OFF
command. This command only affects the control station PLC/PCS [PN] on the precondition
that the commands of this control station are enabled in the relevant mode. It therefore only
has an effect if the control commands of this control station are also active. The "PE
command Start_Pause pending" status is output.
If the motor is already switched off, the "PE energy-saving mode active" status is output. In
this status, the LED "device" flashes green on the basic unit.
Note
Command "Start_Pause"
Use of this function is not meaningful in conjunction with the "overload" control function
because this does not need any control station for routine switch-off and switch-on.