Tables, data records
3.5 Modbus data tables
SIMOCODE pro - Communication
312
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
3.5.2.15
Marking
Read access to the labeling is possible via function codes 03 and 04. Write access is
possible via function codes 06 and 16.
Max. data length per access: 100 registers.
Table 3- 86 Marking
Input/holding register
Identifier
Type
Access
1)
Address
high/low
0x4880
Coordination
Byte[4]
r
0x4882
Reserved
Byte[6]
r/w
0x4885
Marking - external fault 1
Byte[10]
r/w
0x488A
Marking external fault 2
Byte[10]
r/w
0x488F
Marking external fault 3
Byte[10]
r/w
0x4894
Marking external fault 4
Byte[10]
r/w
0x4899
Marking external fault 5
Byte[10]
r/w
0x489E
Marking external fault 6
Byte[10]
r/w
0x48A3
Reserved
Byte[10]
r/w
0x48A8
Reserved
Byte[10]
r/w
0x48AD
Marking limit 1
Byte[10]
r/w
0x48B2
Marking limit 2
Byte[10]
r/w
0x48B7
Marking limit 3
Byte[10]
r/w
0x48BC
Marking limit 4
Byte[10]
r/w
0x48C1
Marking TM1 warning T >
Byte[10]
r/w
0x48C6
Marking TM1 trip T >
Byte[10]
r/w
0x48CB
Marking warning 0/4-20mA >
Byte[10]
r/w
0x48D0
Marking warning 0/4-20mA <
Byte[10]
r/w
0x48D5
Trip marking 0/4-20mA >
Byte[10]
r/w
0x48DA
Trip marking 0/4-20mA <
Byte[10]
r/w
0x48DF
Reserved
Byte[10]
r/w
Data record length: 200 bytes
1) Access to the marking via Modbus: read/write