Tables, data records
3.4 Tables, PROFINET data records
SIMOCODE pro - Communication
240
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
3.4.2.9
Data record 95 - Service data/statistical data
Writing the service data/statistical data
Writing is only possible if password protection is not active.
Additional abbreviations:
●
r / w = value can be written / changed
●
r = value can only be read
Table 3- 60 Data record 95 - service data/statistical data
Byte.Bit
Designation
Type
Range
Unit
Information
0.0
Coordination
Byte[4]
4.0
Permissible starts - Actual value Byte
0 - 255
r
1)
5.0
DM-F - Time until test required Byte
0 - 255
1 week
r
6.0
Reserved
Byte[2]
8.0
Number of parameterizations
Word
0 - 65535
r
10.0
Number of overload trips
Word
0 - 65535
r / w
12.0
Number of internal overload
trips
Word
0 - 65535
r
14.0
Motor stop time
Word
0 - 65535
1 h
r / w
16.0
Timer 1 - Actual value
Word
0 - 65535
100 ms
r
18.0
Timer 2 - Actual value
Word
0 - 65535
100 ms
r
20.0
Timer 3 - Actual value
Word
0 - 65535
100 ms
r
22.0
Timer 4 - Actual value
Word
0 - 65535
100 ms
r
24.0
Counter 1 - Actual value
Word
0 - 65535
r
26.0
Counter 2 - Actual value
Word
0 - 65535
r
28.0
Counter 3 - Actual value
Word
0 - 65535
r
30.0
Counter 4 - Actual value
Word
0 - 65535
r
32.0
Calculation module 1 - Output
Word
0 - 65535
r
34.0
Calculation module 2 - Output
Word
0 - 65535
r
36.0
Reserved
Byte[4]
0
40.0
Motor operating hours
D-word
0 - 0xFFFFFFFF
1 s
r / w
44.0
Int. motor operating hours
D-word
0 - 0xFFFFFFFF
1 s
r
48.0
Device operating hours
D-word
0 - 0xFFFFFFFF
1 s
r
52.0
Number of starts
D-word
0 - 0xFFFFFFFF
r / w
56.0
Internal number of starts CW
D-word
0 - 0xFFFFFFFF
r
60.0
Internal number of starts CCW D-word
0 - 0xFFFFFFFF
r
64.0
Consumed energy
D-word
0 - 0xFFFFFFFF
1 kWh
r / w
UM(+)
68.0
Consumed energy
Float
1 kWh
r
UM+
76.0
Reserved
D-word[6]
100.0
Reserved
Byte[16]
116.0
Timer 5 - Actual value
Word
0 - 65535
100 ms
r