Tables, data records
3.3 Tables, PROFIBUS data records
SIMOCODE pro - Communication
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
157
3.3.2
PROFIBUS data records
3.3.2.1
PROFIBUS data records - general
Data records - Overview
Table 3- 23 Data records - Overview
Data record No.
Description
Read / write
1
S7 system diagnostics (Page 160)
Read
63
Analog value recording (Page 162)
Read
67
Process image output (Page 162)
Read
69
Process image input (Page 163)
Read
72
Error buffer (Page 164)
Read
73
Event memory (Page 164)
Read
92
Device diagnostics (faults, warnings, status information) (Page 165)
Read
94
Measured values (Page 172)
Read
95
Service / statistical data (Page 174)
Read / write
130
Basic device parameters 1 (Page 175) (BU0 BU1 BU2)
Read / write
131
Basic device parameters 2 (Page 181) (BU0 BU1 BU2)
Read / write
132
Extended device parameters 1 (Page 185) (BU2)
Read / write
133
Extended device parameters 2 (Page 193) (BU0 BU2)
Read / write
139
Read / write
160
Communication parameters (Page 198)
Read / write
165
Read / write
202
Read / write
203
Acyclic send (Page 200)
Read
224
Password protection (Page 201)
Write
Writing / reading data records
Access to data records via the slot and index
●
Slot: Access via slot 1
●
Index: Data record number