3.2 Assignment of cyclic receive and send data for predefined control functions
SIMOCODE pro - Communication
138
Function Manual, 11/2018, A5E40508495002A/RS-AC/003
3.2.11
Solenoid valve
Table 3- 14 Assignment of cyclic receive/send data, solenoid valve
Cyclic receive data
Bit 0.0
Not connected
Bit 0.1
Device parameters
→ Motor control → Control stations → PLC/PCS [DP] → Close
Bit 0.2
Device parameters → Motor control → Control stations → PLC/PCS [DP] → Open
Bit 0.3
Further function blocks → Standard functions → Test / Reset → Test1
- Input
Bit 0.4
Not connected
Bit 0.5
Device parameters → Motor control → Control stations → Mode selector S1
Bit 0.6
Further function blocks
→
Standard functions
→
Test / Reset
→
Reset 1
→
Input
Bit 0.7
Not connected
Bit 1.0
Not connected
Bit 1.1
Not connected
Bit 1.2
Not connected
Bit 1.3
Not connected
Bit 1.4
Not connected
Bit 1.5
Not connected
Bit 1.6
Not connected
Bit 1.7
Not connected
Byte 2/3 *) (analog value)
Not connected
Cycl. send data
Bit 0.0
Not connected
Bit 0.1
Status - OFF (CLOSED)
Bit 0.2
Status - ON > (OPEN)
Bit 0.3
Not connected
Bit 0.4
Not connected
Bit 0.5
Status - Remote mode
Bit 0.6
Status - General fault
Bit 0.7
Status - general warning
Bit 1.0
Not connected
Bit 1.1
Not connected
Bit 1.2
Not connected
Bit 1.3
Not connected
Bit 1.4
Not connected
Bit 1.5
Not connected
Bit 1.6
Not connected
Bit 1.7
Not connected
Byte 2/3 (analog value)
Not connected
Byte 4/5 *) (analog value)
Not connected
Byte 6/7 *) (analog value)
Not connected
Byte 8/9 *) (analog value)
Not connected
*) for SIMOCODE pro V / pro S, basic type 1 only