Mounting and connecting the HMI device
3.1 Preparation for mounting
Comfort Panels
32
Operating Instructions, 03/2012, A5E03404994-02
3.1.4
Checking clearances
The following clearances are required around the HMI device to ensure sufficient self-
ventilation:
●
15 mm to the right and 15 mm to the left of the mounting cutout (in the x direction) for
inserting the mounting clamps during installation
●
At least 50 mm above and 50 mm below the mounting cutout (in the y direction) for
ventilation
●
At least 10 mm behind the rear panel of the HMI device (in the z direction)
The following figure shows the clearances during the mounting of the HMI devices in
horizontal and vertical formats:
\
[
[
\
]
\
]
[
[
\
①
Clearance for mounting in horizontal format (all HMI devices)
②
Clearance for mounting in vertical format (Touch HMI devices only)
x
At least 15 mm distance
y
At least 50 mm distance
z
At least 10 mm distance
NOTICE
Ensure that the maximum ambient temperature is not exceeded when mounting the device
in a cabinet and especially in a closed enclosure.
Содержание SIMATIC TP700 Comfort Outdoor
Страница 6: ...Preface Comfort Panels 6 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 12: ...Table of contents Comfort Panels 12 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 24: ...Overview 1 6 Software options Comfort Panels 24 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 28: ...Safety instructions 2 3 Notes about usage Comfort Panels 28 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 136: ...Commissioning the device 4 4 Configuring the device Comfort Panels 136 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 164: ...Operating a project 6 9 Closing the project Comfort Panels 164 Operating Instructions 03 2012 A5E03404994 02 ...
Страница 168: ...Maintenance and care 7 4 Recycling and disposal Comfort Panels 168 Operating Instructions 03 2012 A5E03404994 02 ...