![Siemens Simatic SM331 Скачать руководство пользователя страница 37](http://html.mh-extra.com/html/siemens/simatic-sm331/simatic-sm331_getting-started_1265387037.webp)
Configuration of the SIMATIC Manager
6.2 Hardware configuration
SM331; AI 8x12 Bit Getting Started part 1: 4 -20mA
Getting Started, 11/2006, A5E00253410-02
6-3
Opening the configuration
Double-click on slot 4 that has the SM331 in it.
Select the "Inputs" tab.
Configure the following functions:
●
Diagnostic interrupt enabled
●
Hardware interrupt enabled
●
Input 0-1:
–
Type of measurement: 2DMU
–
Group diagnostics enabled
–
Wire break enabled
●
Input 2-3:
–
Type of measurement: 2DMU
–
Group diagnostics enabled
–
Wire break enabled
●
Input 4-5 and 6-7
–
Type of measurement: Disabled (---)
●
Interference frequency
–
Select your power frequency (50 Hz or 60 Hz)
●
Hardware interrupt trigger
–
Upper limit value 18 mA
–
Lower limit value 6 mA
Figure 6-10 SM331: Configuration