Fail-Safe Blocks
Fail-Safe Systems
A5E00085588-03
8-105
8.10.2 F_TP
Function
The block generates a pulse with the duration PT at the output Q.
The pulse is started by a rising edge at the input IN. The output Q remains set for
the duration PT, irrespective of the subsequent pattern of the input signal.
The output ET indicates how long the output Q has already been set. The
maximum value it can adopt is that of the input PT. It is reset if the input IN
changes to 0, but not before the time PT has elapsed.
If PT < 0, the outputs Q and ET are reset.
Timing Diagram
scasc
Q
IN
PT
ET
PT
PT
PT
Startup Characteristics
In the first cycle after a cold or warm restart or in the case of a first call, the timer is
reset.
I/Os
Name
Data Type
Explanation
Default
Inputs:
IN
F_BOOL
Start input
0
PT
F_TIME
Duration of the pulse
T#0 ms
Outputs:
Q
F_BOOL
Pulse output
0
ET
F_TIME
Elapsed time
T#0 ms
Содержание SIMATIC S7 F
Страница 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Страница 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Страница 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Страница 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Страница 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Страница 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Страница 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Страница 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Страница 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Страница 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Страница 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...