Safety
Fail-Safe Systems
7-10
A5E00085588-03
7.4.2
Calculation of the Minimum Monitoring Times
7.4.2.1 Monitoring the F Cycle Time
The monitoring time is assigned parameters at the MAX_CYC input parameter of
the F_CYC_CO fail-safe blocks.
To ensure monitoring is not triggered when there is no fault, MAX_CYC must be
greater than the maximum cycle time TCImax of the relevant cyclic interrupt OB:
MAX_CYC > TCImax
TCImax is at least as large as the configured cycle time TCI of the cyclic interrupt
OB. In the FH system, the maximum disabling time for priority classes > 15 (TP15)
at updating must also be taken into consideration. Thus the following
approximation formulae apply:
TCImax
≈
TCI + MIN(TCiR, 2500)
In the F system
TCImax
≈
MAX (TCI; TP15) + MIN(TCiR,
2500)
In the FH system with cyclic interrupt OB with
special handling
TCImax
≈
TCI + TP15 + MIN(TCiR, 2500)
In the FH system with cyclic interrupt OB
without special handling
Note the following:
Time
Description
Where to Find it?
TCI
Configured cycle time of the
cyclic interrupt OB
HWCONFIG
CPU properties, "Cyclic Interrupt, Execution"
TP15
Maximum disabling time for
priority classes > 15
HWCONFIG
CPU Properties, "H Parameters"
TCiR
CiR Synchronization Time:
-From the CiR-Object
parameters in STEP7
-Summarize all CiR-Object
synchronization times of the
simultaneously changing DP
buses and place total here.
If CiR is not used, enter 0.
Properties of the CiR_Object in HWCONFIG.
For additional information, refer to section 4.8.4
"Configuration in Run (CiR)".
"Cyclic Interrupt OB with Special Handling" is an H parameter of the CPU in the S7
FH system. The parameter contains the number of the cyclic interrupt OB that is
called separately by the operating system when the standby is updated, after all
the interrupts have been locked. Usually the number of the cyclic interrupt OB with
the highest priority is entered, to which F-blocks of the Safety Program are
assigned in CFC.
Note
To activate the monitoring of the maximum disabling time for priority classes > 15,
you must assign this parameter a value in HWCONFIG (CPU properties, "H
Parameters" tab).
Содержание SIMATIC S7 F
Страница 8: ...Important Information Fail Safe Systems viii A5E00085588 03 ...
Страница 16: ...Contents Fail Safe Systems xvi A5E00085588 03 ...
Страница 38: ...Product Overview Fail Safe Systems 1 22 A5E00085588 03 ...
Страница 56: ...Getting Started Fail Safe Systems 2 18 A5E00085588 03 ...
Страница 70: ...Safety Mechanisms Fail Safe Systems 3 14 A5E00085588 03 ...
Страница 115: ...Programming Fail Safe Systems A5E00085588 03 5 33 Examples Receive Block Send Block ...
Страница 154: ...Programming Fail Safe Systems 5 72 A5E00085588 03 ...
Страница 166: ...Operation and Maintenance Fail Safe Systems 6 6 A5E00085588 03 ...
Страница 332: ...Fail Safe Blocks Fail Safe Systems 8 144 A5E00085588 03 ...
Страница 344: ...References Fail Safe Systems B 2 A5E00085558 03 ...
Страница 350: ...Glossary Fail Safe Systems Glossary 6 A5E00085588 03 ...