Synchronization modules
18.3 Selecting fiber-optic cables
S7-400H
352
System Manual, 03/2012, A5E00267695-11
Table 18- 3 Specification of fiber-optic cables for outdoor applications
Cabling
Components required
Specification
Installation cables for
outdoor applications
Installation cables for outdoor applications
1 cable with 4 cores per fault-tolerant system
Both interfaces in one cable
1 or 2 cables with several shared cores
Separate installation of the interfaces in order to
increase availability (reduction of common cause
factor)
Connector type ST or SC, for example, to match
other components; see below
Further specifications you may need to observe for
your plant:
UL approval
Halogen-free materials
Further specifications you may need to observe for
your plant:
Protection against increased mechanical stress
Protection against rodents
Water-proofing
Suitable for direct underground installation
Suitable for the given temperature ranges
Avoid splicing cables in the field. Use prefabricated
cables with pulling protection/aids in whiplash design,
including measuring log.
including patch cables for
indoor applications as required
1 cable with 4 cores per fault-tolerant system
Both interfaces in one cable
1 or 2 cables with several shared cores
Separate installation of the interfaces in order to
increase availability (reduction of common cause
factor)
Connector type ST or SC, for example, to match
other components; see below
Further specifications you may need to observe for
your plant:
UL approval
Halogen-free materials
Avoid splicing cables in the field. Use prefabricated
cables with pulling protection/aids in whiplash or
breakout design, including measuring log.
A cable junction is required
between the indoor and
outdoor area
see Figure 18-2
Patch cable for indoor
applications
Connector type LC on ST or SC, for example, to
match other components
Содержание SIMATIC S7-400H
Страница 24: ...Preface 1 1 Preface S7 400H 24 System Manual 03 2012 A5E00267695 11 ...
Страница 46: ...Getting Started 4 5 Special layout features of SIMATIC Manager S7 400H 46 System Manual 03 2012 A5E00267695 11 ...
Страница 120: ...Memory concept 10 1 Overview of the memory concept of S7 400H CPUs S7 400H 120 System Manual 03 2012 A5E00267695 11 ...
Страница 258: ...Communication 14 8 General issues regarding communication S7 400H 258 System Manual 03 2012 A5E00267695 11 ...
Страница 354: ...Synchronization modules 18 3 Selecting fiber optic cables S7 400H 354 System Manual 03 2012 A5E00267695 11 ...
Страница 434: ...Technical data 20 6 Runtimes of the FCs and FBs for redundant I Os S7 400H 434 System Manual 03 2012 A5E00267695 11 ...
Страница 460: ...Function modules and communication processors supported by the S7 400H S7 400H 460 System Manual 03 2012 A5E00267695 11 ...