Firmware updates
5.8.1
Subsequent Loading of Firmware Updates
You can download the firmware update to the operating system memory of the CP 341 in
order to expand its functionality and for error handling.
Requirements
The requirements for loading firmware updates are as follows:
●
STEP 7 V5.3 and higher
●
You must first create a valid project in HW Config and load it onto the CPU before you
can update the firmware of the CP.
●
The CP 341 must be available online on the PG/PC.
●
Refer to the instructions for the firmware update package for the storage location of the
firmware update files.
The "..\CP341.nnn" path always identifies the firmware version.
Load firmware in HW Config
(valid as of order number 6ES7341-1_H02-0AE0)
Carry out a firmware update as follows:
1. Switch the CPU to STOP mode.
2. Open HW Config, then select the relevant CP 341 module.
3. Select the menu command PLC > Update Firmware.
For additional information on procedures, refer to the
STEP 7 online help.
The system outputs a message to indicate successful completion of the update and
immediately activates the new firmware.