WARNING
No cable or line entries or simple designs of sealing plug may be used on terminal boxes
with the "Ex e" type of protection.
An explosion may occur during operation. This can result in death, serious injury or material
damage.
● Use only cable entries that have been tested and certified in accordance with
IEC / EN 60079–7 .
● Use only sealing plugs that have been tested and certified in accordance with
IEC / EN 60079–7 to close openings that are not to be used.
CAUTION
Working on terminal boxes of the "Ex e" type of protection with undrilled cable entry plate
This can result in death, serious injury or material damage.
Ensure that the cable entry plate is still strong enough after drilling the threads.
6.2.4
Connecting the grounding conductor
The cross-section of the machine grounding conductor must comply with the installation
regulations and also with IEC / EN 60204-1.
Table 6-2
Determining the cross-section of the grounding conductor
External cable cross-section S
Cross-section of the grounding conductor [mm²]
S ≤ 16 mm²
S
16 mm² < S ≤ 35 mm²
16 mm²
S > 35 mm²
S/2
A terminal strip for grounding is fitted either on the stator casing or on the flanged endshield,
depending on the frame size. The grounding point is marked.
The terminal strip is suitable for connecting stranded cables with cable lugs or connecting flat
straps. In addition, all motors have a PE terminal within the terminal box.
When connecting up the grounding conductor, ensure that the contact surface of the
connection is bare and protected against corrosion using a suitable agent, e.g. with acid-free
Vaseline.
6.2.5
Circuit diagram in the terminal box cover
Data on the connection and connecting the motor winding can be found in the circuit diagram
in the cover of the terminal box.
Electrical connection
6.2 Connecting
LOHER CHEMSTAR 1PS5
58
Operating Instructions 03/2014
Содержание SIMATIC S5 1P 243
Страница 2: ...11 03 2014 02 49 V4 00 ...
Страница 12: ...Introduction LOHER CHEMSTAR 1PS5 12 Operating Instructions 03 2014 ...
Страница 20: ...Safety notes 2 11 Ventilation LOHER CHEMSTAR 1PS5 20 Operating Instructions 03 2014 ...
Страница 42: ...Preparations for use 4 11 Converter operation LOHER CHEMSTAR 1PS5 42 Operating Instructions 03 2014 ...
Страница 66: ...Electrical connection 6 2 Connecting LOHER CHEMSTAR 1PS5 66 Operating Instructions 03 2014 ...
Страница 124: ...Disposal 11 4 Disposal of components LOHER CHEMSTAR 1PS5 124 Operating Instructions 03 2014 ...
Страница 126: ...Service and Support A 1 Siemens Service Center LOHER CHEMSTAR 1PS5 126 Operating Instructions 03 2014 ...
Страница 136: ...Quality documents C 4 Data LOHER CHEMSTAR 1PS5 136 Operating Instructions 03 2014 ...
Страница 140: ...Index LOHER CHEMSTAR 1PS5 140 Operating Instructions 03 2014 ...
Страница 141: ...AC EC Declaration of Conformity U161 AB EC Declaration of Conformity U163 AA R No 20000h U165 ...