Device description
2.2 PLB Basic module
Power Line Booster
16
Operating Instructions, 11/2019, A5E36203125A-AG
Table 2- 4
LED PLB BM
LED labeling
Meaning
Color
State
Description
PWR
Power
Green
Off
24 V supply missing or too low
On
LED test for about 0.5 s during startup
24 V supply
PWR PL
Power - powerline
Green
Off
Normal operation
Flashes (ap-
prox. 1 Hz)
Short-circuit of a powerline cable to PE or L1, L2
or L3
On
LED test for about 0.5 s during startup
RN
Run
Green
Off
Startup
Flashes (ap-
prox. 1 Hz)
Waiting for PROFINET connection or operation
without PROFINET
Station flash test (PN) together with the port LEDs
of the ET200SP BusAdapter (BA)
Flashes (ap-
prox. 4 Hz)
Firmware update of the basis in progress (togeth-
er with ER and MT)
On
LED test for about 0.5 s during startup
PN-AR with IO data exchange
ER
Error
Red
Off
No error
Flashes
(approx. 1 Hz)
Station flash test (PN) together with the port LEDs
of the ET200SP BusAdapter (BA)
External error: Short-circuit between a phase and
Rail A or Rail B
External error: Ground fault of Rail A or Rail B
Flashes (ap-
prox. 4 Hz)
Firmware update of the basis in progress (togeth-
er with RN and MT)
On
LED test for about 0.5 s during startup
2 modems inserted or modem installed incorrectly
MT
Maintenance
Yellow
Off
No maintenance required
Flashes
(approx. 1 Hz)
Station flash test (PN) together with the port LEDs
of the ET200SP BusAdapter (BA)
Flashes (ap-
prox. 4 Hz)
Flashes synchronously with the LEDs of the PLB
MM
•
Firmware update of the modem module is
running.
•
When restarting after a configuration change
a)
Flashes (ap-
prox. 4 Hz)
Firmware update of the basis in progress (togeth-
er with ER and RN)
On
LED test for about 0.5 s during startup
Maintenance required: e.g. FW update has failed.
A new update is necessary.
MS
Master
Green
Off
PLB slave
On
LED test for about 0.5 s during startup
PLB master